Watlow LogicPro Manuale Utente Pagina 51

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 296
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 50
LogicPro User’s Guide Chapter 4: Resources
Doc.# 28002-00 Rev 3.00 Watlow Anafaze 35
To configure communications with the PPC-2000:
1. Select the correct Communication Port for your PC.
2. Select a Parity of Even, Odd or None.
3. In the Device Address field, enter the controller
address for the PPC-2000.
4. In the ROM Size field, enter 128kB. (Controllers with
2.03 and earlier firmware support up to 40 kB.
5. Select a Baud Rate. The PPC-2000 supports 9600 and
19200.
6. In the Time out field, enter 2000 milliseconds.
7. Click [OK]
-or-
Click [Cancel] to exit this screen.
CPC400 Attributes
The CPC400 has the following default communication
settings:
Baud Rate: 19200
Controller Address: 1
To configure communications with the CPC400:
1. Select the correct Communication Port for your PC.
2. Select a Parity of None.
3. In the Device Address field enter the controller
address you set in the CPC400.
4. In the ROM Size field, enter 64 kB.
5. Select a Baud Rate. The CPC400 supports 2400, 9600
and 19200.
6. In the Time out field enter 2000 milliseconds.
7. Click [OK]
-or-
Click [Cancel] to exit this screen.
Vedere la pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 295 296

Commenti su questo manuale

Nessun commento