ANAFAZE 12LS
Installation And Operation Manual
Revision 3
August 1, 1991
Copyright (c) 1990
Watlow Anafaze, Incorporated
334 Westridge Dr
Watsonville, CA 95076
Phone: 831-724-3800
Facsimile: 831-724-0320
All RIGHTS RESERVED: No part of this publication may be reproduced, stored in a retrieval
system or transmitted in any form by any means; electronic, mechanical, photo copying,
recording, or otherwise, without the prior written permission of ANAFAZE, Inc.
Printed in U.S.A.
Vedere la pagina 0
1 2 3 4 5 6 ... 110 111

Sommario

Pagina 1

ANAFAZE 12LSInstallation And Operation ManualRevision 3August 1, 1991Copyright (c) 1990Watlow Anafaze, Incorporated334 Westridge DrWatsonville, CA 950

Pagina 2

1-3Guided Menus Simplify SetupThe ANAFAZE 12LS directs operator and supervisor changes with guided menus. Two levels areprovided: one for operator ch

Pagina 3

7-2If the address is not changed the unit will probably have the default address 1. If the addressmust be changed on line, ANASOFT will indicate comm

Pagina 4

7-3If ANASOFT runs then the next step is to establish communications with the 12LS. On start upANASOFT checks communication with the controller. If

Pagina 5

8-18.0 SOFTWARE COMMAND STRUCTUREThe 12LS will respond to commands according to the following format. The commandsgenerally follow the specifications

Pagina 6

8-2 Data Boundary ErrorThis Error Code is returned when: - A Read command attempts to read beyond the 32 byte boundary of byte-size vari

Pagina 7

8-3. Input TypesThe following one byte codes designate the various input types accepted by the 12LS: Code Input Type

Pagina 8 - 1.0 INTRODUCTION

8-4The following examples show the output code for specific output types: Output Configuration Hex Code-------------

Pagina 9

G-19.0 GLOSSARY OF TERMSAddress The ANAFAZE controller address used in computercommunications. Each controller must have aseparate address b

Pagina 10

G-2Cycle Time The time base for the time proportioning outputsentered in seconds. For example with a 10 secondcycle time, and 30% output, the outpu

Pagina 11

G-3Scaling Enter two values of unscaled process readings RDGand their corresponding scaled process values PV.Try to have as near as possible to

Pagina 13

1-4Digital Inputs and Outputs Expand VersatilityDigital inputs and outputs are provided to further enhance the ANAFAZE 12LS flexibility. Digitaloutpu

Pagina 14

Congratulations! You have obtained one of the fineproducts from the ANAFAZE Incorporated line of qualityMeasurement and Control

Pagina 16

2-12.0 SPECIFICATIONS2.1 Analog InputsAnalog Inputs 12, Solid state, common ground.Isolation: Between inputs and ground: 10v

Pagina 17

2-22.2 Control CapabilityNumber of Loops: 12, Dual Output.Control Outputs: Cycle Time Proportioning, Distributed Zero Crossing, or On/Off;all

Pagina 18 - 3.1.2 EXTERNAL WIRING

2-3Power input: 10 to 30VDC, 3 Watts typical, 110VAC adapter provided.

Pagina 19

3-13.0 INSTALLATIONThere are some precautions that must be observed when installing ANAFAZE 12LS. WARNING! -- ELECTRICAL SHOCK DANGER It

Pagina 20 - 3.1.4 RECOMMENDED CABLES P/N

3-23.1.1 MOUNTINGFor optimum performance when directly connecting thermocouple inputs the unit should beprotected from thermal shocks whenever possi

Pagina 21

3-3 1/8th DIN HOUSING

Pagina 22

3-43.1.2 EXTERNAL WIRINGDuring wiring, it is recommended that the 12LS electronics be removed or temporary covers be put over the housingslots to ensu

Pagina 23

3-54. Use Thermocouple Extension Wire for all thermocouple (T/C) inputs. Most T/C Ext. Wire is solid wireunshielded. When using such, the shield

Pagina 24 - 3.3.3GROUNDING

iiSTATEMENT OF WARRANTYANAFAZE, Incorporated warrants that the Products furnished under this Agreement will be freefrom material defects in material a

Pagina 25 - 3.3.5 INPUT SCALING

3-63.1.4 RECOMMENDED CABLES P/NUse these cables or equivalent. |--------------------------------------------------------------| ¦ FUNCTION

Pagina 26 - 3.3.8THERMOCOUPLE INPUTS

3-73. Separate the 120 vac power leads from the low level input and outputs leads from the ANAFAZE. Do not run thedigital outputs or PID control outpu

Pagina 27 - 3.3.9RTD INPUTS

3-83.2 TERMINAL BLOCK AND CONNECTOR LAYOUTThe ANAFAZE 12LS terminal blocks and connectors are assigned according to the following two pages. Subseque

Pagina 28 - 3.4 CONTROL OUTPUTS

3-9 REMOTE TERMINAL BLOCK CONNECTIONSThe remote terminal block (RTB) provides the control outputs and additional digital inputs and out

Pagina 29 - 3.4.2 PID OUTPUT LIMITING

3-103.3 ANALOG INPUTSConnecting analog signals to the ANAFAZE 12LS is normally straightforward. Most thermocouples can be directlyconnected and mixed

Pagina 30 - 3.5.2 OTHER RS-232 LINES

3-113.3.5 INPUT SCALINGThe ANAFAZE 12LS contains an area that can be used to install resistors to scale input voltages and convert milliampinputs to m

Pagina 31 - 3.5.3 RS-485 DESCRIPTION

3-123.3.6 VOLTAGE INPUTSDC Voltage inputs should be connected with the positive side to the CH +IN terminal and the negative side to one ofthe -IN COM

Pagina 32

3-13 WARNINGUse of the grounded T/C, meaning that the T/C junction is at the same potential of the metal protection sheath

Pagina 33

3-14If desired, a second input may be used to monitor the internal IRSM ambient temperature. Consult ANAFAZE formore information.3.3.11 SCALING AND CA

Pagina 34

3-153.4.1 PID CONTROL AND ALARM OUTPUTS CONNECTIONSTypical digital control outputs utilize external optically- isolated solid-state relays. These rel

Pagina 35

iiiWARNINGANAFAZE HAS MADE EFFORTS TO ENSURE THE RELIABILITY AND SAFETY OFTHE 12LS AND PROVIDE RECOMMENDATIONS FOR ITS SAFE USE IN SYSTEMSAPPLICATIONS

Pagina 36 - 4.1 FRONT PANEL KEYS

3-163.5 COMPUTER SERIAL COMMUNICATIONSThe ANAFAZE 12LS offers two types of serial communications: RS- 232 and RS-485. The RS-232 is used primarilyfor

Pagina 37 - 4.2.1 BAR GRAPH DISPLAY

3-173.5.3 RS-485 DESCRIPTIONThe EIA Standard RS-485 specifies only the electrical characteristics of generators (transmitters) and receivers for usein

Pagina 38 - 4.2.2 SINGLE LOOP DISPLAY

3-183.5.3.2 RS-485 CONNECTIONSConnection of ANAFAZE controllers to a system computer requires an interface at the computer to convert RS-232levels to

Pagina 39 - 4.2.3 SCANNING DISPLAY

3-19ANAFAZE 12LS connections for a single unit are as follows:Black Box 12LSLD485A

Pagina 40 - 4.2.4 ALARM DISPLAY

4-14.0 FRONT PANEL OPERATION AND DISPLAYSThe 12LS front panel provides the operator interface for the controller. The 12LS may be fullyprogrammed and

Pagina 41

4-2 |- - - - - - - - - - - - - -|

Pagina 42 - 4.4.1 CHANGE SETPOINT

4-34.1 FRONT PANEL KEYSThe four main function keys on the front panel are used to perform specific operations : |-----| o Adjust the setpoint on

Pagina 43 - 4.4.2 SET LOOP TO MANUAL/AUTO

4-44.2 DISPLAYSOn power-up the controller defaults to the BAR GRAPH display which shows the status of all 12 loops.From there the user may switch to t

Pagina 44 - 4.5 SETUP MENUS

4-54.2.2 SINGLE LOOP DISPLAYThe SINGLE LOOP Display shows the detailed information for one loop at a time. The UP/DOWN arrows select theloop number.

Pagina 45

4-6|--------------------------------------------------------------|¦ Table 4-1. LOOP STATUS DEFINITIONS ¦|------------------

Pagina 46

ivANAFAZE 12LSTABLE OF CONTENTS1.0 INTRODUCTION...

Pagina 47

4-74.2.4 ALARM DISPLAYThe ALARM display interrupts any system display. If more than one alarm is present the first alarm is shown. |-----------

Pagina 48

4-84.3 GENERAL PROGRAMMING AND EDITINGIn general, the 12LS menu structure consists of several main menus each having a group of sub-menus beneath them

Pagina 49

4-94.4 OPERATIONAL MENUSAll changes must start from the SINGLE LOOP display. The following changes can be made by pressing theassociated front panel k

Pagina 50

4-104.4.2 SET LOOP TO MANUAL/AUTOTo toggle the current mode from MANUAL to AUTO or from AUTO to MANUAL, press this key : |----|

Pagina 51

4-114.5 SETUP MENUSTo change any other of the controller settings select the loop desired and from the SINGLE LOOP display enter thepassword key seque

Pagina 52 - 4.5.2 SETUP LOOP INPUT

4-12LOOP SETUP DATA|--------------------------------------------------------------|¦Date _________ ¦¦

Pagina 53

4-13 |-----------------------------------------------------| ¦ NOTE: Unless otherwise specified, in all examples ¦ ¦of menu displays in

Pagina 54

4-14The menu appears as: |----------------| ¦SAVE CURRENT ¦ ¦SETUP TO JOB ? x¦ |-----------

Pagina 55

4-15Press ENTER to store the new alarm delay setting or press BACK to return to the SETUP GLOBAL PARAMETERSmain menu heading.4.5.1.4 SETTING THE GLOBA

Pagina 56

4-164.5.1.6 POWER UP OUTPUT STATUSThis menu is used to configure the initial power-up state of the control outputs. The controller will either initial

Pagina 57

v4.4 OPERATIONAL MENUS...4-94.4.1 CHANGE SETPOINT...

Pagina 58 - 4.5.4 SETUP LOOP OUTPUTS

4-174.5.1.8 COMMUNICATION ERROR CHECKING METHODThis menu is used to select the checksum algorithm used in the ANAFAZE communications protocol. Either

Pagina 59

4-18Press YES to select the menu or NO to advance to the next menu.Press UP and DOWN to toggle the selection between 9600 and 2400.Press ENTER to stor

Pagina 60

4-194.5.2 SETUP LOOP INPUTPress YES at this prompt to access menus to change parameters related to the channel input including : o Input typ

Pagina 61 - 4.5.5 SETUP ALARMS

4-20The display appears as : |----------------| ¦LL INPUT ¦ ¦ UNITS ? xxx ¦ |-------

Pagina 62

4-21The display for the high process variable will appear as : |----------------| ¦LL INPUT SCALING¦ ¦HIGH P

Pagina 63

4-22The low input reading is referenced to 60mV and is calculated using this equation: (see section 3.3.6) (Sensor

Pagina 64

4-23When the PV readout is reading below the true known PV level, add that amount to the High and Low PV scaling.When the PV readout is reading above

Pagina 65 - 4.5.6 MANUAL I/O TEST

4-244.5.3.1 PROPORTIONAL BANDThe first selection for each output allows programming of the proportional band. The display bottom line appears as :

Pagina 66

4-254.5.3.4 OUTPUT FILTERThis menu allows allows programming of the output filter. The output filter causes the controller to average multipleoutput c

Pagina 67

4-26 |-----------------------------------------------------| ¦ NOTE: If the channel is operating as a single output¦ ¦loop (ref. 4.5.3) al

Pagina 68

vi6.0 SOFTWARE ...6-16.1 ANASO

Pagina 69

4-274.5.4.2 CYCLE TIMEIf Time Proportioning is selected as the output type the controller will prompt the user for a cycle time. The lowerdisplay will

Pagina 70

4-28Press UP and DOWN to set the maximum output power percentage from 0 t 100%.Press ENTER to store the output limit or BACK to return to the SETUP L

Pagina 71

4-294.5.5.1 HIGH PROCESS ALARM SETPOINTThis menu is used to set the point within the scaled sensor range at which the high process alarm is activated.

Pagina 72

4-304.5.5.4 DEVIATION BAND ALARMThis menu is used to set the deadband alarm value. The deviation alarm is a plus and minus alarm that is alwaysrelativ

Pagina 73

4-31Press ENTER to store the output assignment or press BACK to return to the SETUP LOOP ALARMS main menuprompt.4.5.5.7 LOW DEVIATION ALARM OUTPUT ASS

Pagina 74

4-32Press ENTER to store the status or press BACK to return to the SETUP LOOP ALARMS main menu prompt.4.5.5.10 LOW PROCESS ALARM OUTPUT ASSIGNMENTThis

Pagina 75

4-334.5.6.1 DIGITAL INPUT TESTINGThis is a view-only display showing the logic state of the 8 digital inputs as 1's (High) or 0's (Low). The

Pagina 76

4-344.6 RAMP AND SOAK OPTIONThe ramp and soak option turns the 12LS into a powerful batch controller. Along with the powercomes a certain amount of c

Pagina 77

4-354.6.1 DESCRIPTIONA ramp / soak profile consists of several groups of parameters: those global to the profile as a unit,those defined as the "

Pagina 78

4-36+-------------------------------------------------------------+¦ PARAMETERS SPECIFIC TO EACH SEGMENT ¦|-------------------

Pagina 80

4-37This function may be enabled or disabled per segment via the tolerance parameter. If tolerance isOFF no guarantee of setpoint is made and the tole

Pagina 81

4-384.6.3 PROFILE STATUS DISPLAYWhether in the TIME display, the CYCLE COUNT display or the PROFILE OPERATION menu,the upper line of the display will

Pagina 82

4-39Use the UP and DOWN keys to change the profile letter. Profile assignment may be 'A' to 'L' forone of the twelve ramp and soak

Pagina 83

4-40An example display follows: |----------------| ¦05 A SEG01/07 R ¦ ¦TIME LEFT= 34:28¦ |----

Pagina 84

4-41|--------------------------------------------------------------|¦ TABLE 4-2 Ramp / Soak Operations ¦|-----------------

Pagina 85

4-42 |----------------------------------------------------| ¦ NOTE: When leaving ramp and soak mode the loop is ¦ ¦ placed in MANUAL mode and the

Pagina 86

4-43 PROFILE SETUP GUIDE

Pagina 87

4-44 PROFILE SETUP GUIDE

Pagina 88

4-45 |-----------------------------------------------------| ¦ NOTE: For RAMP AND SOAK option, if the loop is run- ¦ ¦ ning a ramp and soak profile, f

Pagina 89

4-46UP/DOWN Select a profile designator [A-L].

Pagina 90

1-11.0 INTRODUCTIONThe ANAFAZE 12LS is a powerful 1/8th DIN controller that delivers 12 fully independent loopsof PID control. It functions as both

Pagina 91

4-47ENTER Open the selected profile for editing. The display advances to theCopy Profile Menu. BACK Return to SETUP R

Pagina 92 - 5.0 PID CONTROL

4-48When any segment is out of tolerance for a period greater than the Tolerance Time entered, atolerance alarm is generated. A tolerance alarm activa

Pagina 93

4-49 ENTER Store new ready state setpoint. Display will advance to Edit Ready EventStates. BACK Return to

Pagina 94

4-504.7.6 EDIT EXTERNAL RESETFrom this menu one of the eight digital inputs will be selected to provide an input for a externalreset of this profile w

Pagina 95

4-51 NO Select the default segment for editing. Display advances to Edit SegmentTime. BACK Return t

Pagina 96

4-52YES Change current setpoint setting. Lower display SP =xxxx UP/DOWN Changes setpoint value. ENTER

Pagina 97

4-53YES Change the output assigned to this event. Lower display DOUT= xx UP/DOWN Select output number. [1-30, NO].

Pagina 98 - 6.0 SOFTWARE

4-544.7.13 EDIT SEGMENT TRIGGERSUse this menu to edit the trigger input assignments, their active states and their latching status forthe current segm

Pagina 99

4-55 YES Edit input number assigned to this trigger. Lower display DIN = xx UP/DOWN Select input nu

Pagina 100

4-564.7.16 EDIT TRIGGER LATCH STATUS |--------------|Display: ¦ a SEG TR DI¦ ¦ TRIG? UNLATCH¦ |-----

Pagina 101

1-2The ANAFAZE 12LS front panel provides an intelligent method for both viewing the processconditions and operating the controller. Displays show inf

Pagina 102

4-57 YES Change current tolerance value. Lower display TOL = xx UP/DOWN Set value [+99]

Pagina 103

4-584.7.19 EDIT PROFILE CYCLESThis menu is used to enter the desired cycles for this profile. Cycles is the number of times thisprofile is to be repea

Pagina 104

5-15.0 PID CONTROLThe information provided in this manual is provided to get the system up and running with aminimum of effort. For further details o

Pagina 105

5-25.1.5 DISTRIBUTED ZERO CROSSINGDistributed Zero Crossing [DZC] output is the other time proportioning output available from the12LS. This output i

Pagina 106 - 9.0 GLOSSARY OF TERMS

5-35.2.2 PROPORTIONAL WITH INTEGRAL CONTROL:The Two-mode PI is the most common of the control modes in use in industry. It must be tunedby tuning the

Pagina 107

5-4There is no tuning step for the Output Filter. Adjusting the PID without the Filter(set at 0) willgive the fastest output response to a step change

Pagina 108

5-55.2.5 PID TUNING CONSTANTS PROPORTIONAL BAND SETTINGSTHE FOLLOWING TABLE REPRESENTS AN AVERAGE SETTING FOR THE PB INRELATIONSHIP

Pagina 109

5-65.2.6 GENERAL PID CONSTANTS BY APPLICATIONPROPORTIONAL BAND ONLY (P)PB = SET 7% of SP Example: SP = 450 PB = 31TI = OFFTD = OFFOutput Filter =

Pagina 110

6-16.0 SOFTWAREANAFAZE offers turnkey software for IBM PC and compatible computers. The presentsoftware includes:ANASOFT-SV Standard Version for

Pagina 111

7-17.0 TROUBLE SHOOTING INFORMATION7.1 Stand Alone SystemsFor stand alone systems the ANAFAZE 12LS should be returned to ANAFAZE when problemsoccur.