Watlow EZ-ZONE
®
RML Module 100 Chapter 6 Features
Math
Average
Range Low
Range High
Pressure Units
Altitude Units
Scale Low
Scale High
Function
Filter
Offset
Filter
Output Value = Filter [(Average (A + B + C +
D)) + Offset] Display units follows the last
source that is temperature else follow Source A
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Value A
Source Value B
Source Value C
Source Value D
Source Value E
Output Value
Error
Math
Deviation Scale
Range Low
Range High
Pressure Units
Altitude Units
Scale Low
Scale High
Function
Filter
Offset
Filter
If E = OFF, Output Value = Filter
[((Range High - Range Low) / (Scale High
- Scale Low)) * (A - Scale Low) + Range
Low + B + Offset] If E = ON, Output
Value = Filter [B + Offset] Scale Low/High
and Range Low/High follows Source A
display units.
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Value A
Source Value B
Source Value C
Source Value D
Source Value E
Output Value
Error
Math
Switch Over
Range Low
Range High
Pressure Units
Altitude Units
Scale Low
Scale High
Function
Filter
Offset
Filter
If E = OFF, Output Value = Filter [A +
Offset] If E = ON, Output Value =
Filter [B + Offset] Display units
follows active source.
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Value A
Source Value B
Source Value C
Source Value D
Source Value E
Output Value
Error
Math
Ratio
Range Low
Range High
Pressure Units
Altitude Units
Scale Low
Scale High
Function
Filter
Offset
Filter
Output Value = Filter [(A / B) + Offset]
If display units of Source A = Source B,
no display units on output value, else
follow Source A
Source Function A
Source Instance A
Source Zone A
Source Error A
Source Function B
Source Instance B
Source Zone B
Source Error B
Source Function C
Source Instance C
Source Zone C
Source Error C
Source Function D
Source Instance D
Source Zone D
Source Error D
Source Function E
Source Instance E
Source Zone E
Source Error E
Source Value A
Source Value B
Source Value C
Source Value D
Source Value E
Output Value
Error
Vedere la pagina 102
1 2 ... 98 99 100 101 102 103 104 105 106 107 108 ... 126 127

Commenti su questo manuale

Nessun commento