LogicPro Users Guide Chapter 12: Function Blocks
Doc.# 28002-00 Rev 3.00 Watlow Anafaze 199
Digital_In_207x
The Digital_In_207x driver supports the inputs on the PPC-207x
Digital In series modules.
To associate a variable with a digital input:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select BOOL from the Type list.
4. Select Input by clicking the check box.
5. Select Digital_In_207x from the IO Driver list.
6. Enter the IO Physical Address. The address is:
X.Z X is the module address (51-54)
Z is the module I/O number (1-16)
7. Click [OK].
PPC-207x Digital In Addressing Example
To create a variable named In_5 that examines the state of the fifth
input on a PPC-207x module with its rotary address switch set to 52,
set the options in the Add Program/Resource Variable dialog
box as illustrated below.