Watlow MLS Manuale Utente Pagina 102

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 101
90 MLS User’s Guide
Setup
Alarm Delay
You can set the MLS to delay normal alarm detection and alarm
reporting. There are two kinds of alarm delay:
The startup alarm delay delays process alarms (but not failed sensor
alarms) for all loops for a time period you set in the Setup Global
Parameters main menu.
The loop alarm delay delays failed sensor alarms and process alarms
for one loop until the alarm condition is continuously present for
longer than the loop alarm delay time you set.
NOTE
Failed sensor alarms are affected by the loop alarm
delay even during the startup alarm delay time period.
Vedere la pagina 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 141 142

Commenti su questo manuale

Nessun commento