Watlow Series PD ■ 10 ■ Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Note: Current transformer (CT)
must be purchased separately.
Note: A current transformer input
cannot be associated with a
process output on Output 1 or 3.
Figure 10a — Digital input internal circuit
Dual Current Transformer (CT) Inputs
PD_ 3-_ _ _ _-_ _ _
• Input impedance 100Ω, Vac only.
The current transformer (CT) must be purchased separately. Watlow CT
part number is 16-0246 (up to 50 amps).
Systems that are more than 50 amps need an interstage transformer. For
example, if you use a 300 amp CT, part number 16-0073, and an interstage
transformer, part number 16-0176, the 300 amp CT provides a 5 amp signal
to the interstage transformer. In turn, the interstage transformer provides a
20 mA maximum signal to the controller.
Figure 10b — Single Phase