Chapter 12: Function Blocks LogicPro User’s Guide
192 Watlow Anafaze Doc.# 28002-00 Rev 3.00
Using the IO Drivers
The following sections describe and illustrate the use of each IO
Driver.
Processor_2010
The Processor_2010 driver supports the digital I/O on board the
PPC-2010 Processor module.
To associate a variable with a digital I/O point:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select BOOL from the Type list.
4. Select Input or Output by clicking the corresponding check
box.
5. Select Processor_2010 from the IO Driver list.
6. Enter the IO Physical Address. The address is:
0.0.ZZ is the module I/O number (1-48)
7. Click [OK].
To associate a variable with the pulse input:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select INT from the Type list.
4. Select Input by clicking the check box.
5. Select Processor_2010 from the IO Driver list.
6. Select WORD from the IO Size list.
7. Enter the IO Physical Address. The address is:
0.Y.1 Y is the type of I/O (1 = Count, 2 = Frequency)
8. Click [OK].